| Partner Name | Transit Electrical Pty Ltd |
|---|
| State | WA |
|---|
| Date of Visit | 16/11/2025 |
|---|
| Technician's Name | James Ciupac |
|---|
| Which Company are you working for? | Sturdie Trade Services |
|---|
| Sturdie Job Number | 50F0682/0012 |
|---|
| Email | Email hidden; Javascript is required. |
|---|
| The Good Guys Site in WA | mandurah |
|---|
|
|
|---|
| Location Name | Mandurah |
|---|
| |
|---|
| HTML Block |
|
|---|
| Test Period | 12 Monthly (90 minutes) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| Carry out push button test for correct operation | |
|---|
| HTML Block |
|
|---|
| Carry out test with RCD Tester | Carry out push button test and record the results below. |
|---|
| RCD Details (Initial/12 Months) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| DB 01 |
R1 |
Y |
P |
|
|
| DB 01 |
W1 |
Y |
P |
|
|
| DB 01 |
B1 |
Y |
P |
|
|
| DB 01 |
R2 |
Y |
P |
|
|
| DB 01 |
W2 |
Y |
P |
|
|
| DB 01 |
B2 |
Y |
P |
|
|
| DB 01 |
R3 |
Y |
P |
|
|
| DB 01 |
W3 |
Y |
P |
|
|
| DB 01 |
B3 |
Y |
P |
|
|
| DB 01 |
R4 |
Y |
P |
|
|
| DB 01 |
W4 |
Y |
P |
|
|
| DB 01 |
B4 |
Y |
P |
|
|
| DB 01 |
R5 |
Y |
P |
|
|
| DB 01 |
W5 |
Y |
P |
|
|
| DB 01 |
B5 |
Y |
P |
|
|
| DB 01 |
R6 |
Y |
P |
|
|
| DB 01 |
W6 |
Y |
P |
|
|
| DB 01 |
B6 |
Y |
P |
|
|
| DB 01 |
R7 |
Y |
P |
|
|
| DB 01 |
R8 |
Y |
P |
|
|
| DB 01 |
W8 |
Y |
P |
|
|
| DB 01 |
B8 |
Y |
P |
|
|
| DB 01 |
W9 |
Y |
P |
|
|
| DB 01 |
R10 |
Y |
P |
|
|
| DB 01 |
W10 |
Y |
P |
|
|
| DB 01 |
B10 |
Y |
P |
|
|
| DB 01 |
R11 |
Y |
P |
|
|
| DB 01 |
W11 |
Y |
P |
|
|
| DB 01 |
B11 |
Y |
P |
|
|
| DB 01 |
R12 |
Y |
P |
|
|
| DB 01 |
W12 |
Y |
P |
|
|
| DB 01 |
B12 |
Y |
P |
|
|
| DB 01 |
R13 |
Y |
P |
|
|
| DB 01 |
W13 |
Y |
P |
|
|
| DB 01 |
B13 |
Y |
P |
|
|
| DB 01 |
R14 |
Y |
P |
|
|
| DB 01 |
W14 |
Y |
P |
|
|
| DB 01 |
B14 |
Y |
P |
|
|
| DB 01 |
R15 |
Y |
P |
|
|
| DB 01 |
W15 |
Y |
P |
|
|
| DB 01 |
B15 |
Y |
P |
|
|
| DB 01 |
R16 |
Y |
P |
|
|
| DB 01 |
W16 |
Y |
P |
|
|
| DB 01 |
B16 |
Y |
P |
|
|
| DB 01 |
R17 |
Y |
P |
|
|
| DB 01 |
W17 |
Y |
P |
|
|
| DB 01 |
B17 |
Y |
P |
|
|
| DB 01 |
R18 |
Y |
P |
|
|
| DB 01 |
W18 |
Y |
P |
|
|
| DB 01 |
B18 |
Y |
P |
|
|
| DB 01 |
B19 |
Y |
P |
|
|
| DB 01 |
R20 |
Y |
P |
|
|
| DB 01 |
RWB21,RW23 |
Y |
P |
|
|
| DB 01 |
B23 |
Y |
P |
|
|
| DB 01 |
R26 |
Y |
P |
|
|
| DB 01 |
W26 |
Y |
P |
|
|
| DB 01 |
B26 |
Y |
P |
|
|
| DB 01 |
R28 |
Y |
P |
|
|
| DB 01 |
W28 |
Y |
P |
|
|
| DB 01 |
B28 |
Y |
P |
|
|
| DB 01 |
R33 |
Y |
P |
|
|
| DB 01 |
W33 |
Y |
P |
|
|
| DB 01 |
B33 |
Y |
P |
|
|
| DB 01 |
R34 |
Y |
P |
|
|
| DB 01 |
W34 |
Y |
P |
|
|
| DB 01 |
B34 |
Y |
P |
|
|
| DB 01 |
R35 |
Y |
P |
|
|
| DB 01 |
W35 |
Y |
P |
|
|
| DB 01 |
B35 |
Y |
P |
|
|
| DB 01 |
R36 |
Y |
P |
|
|
| DB 01 |
W36 |
Y |
P |
|
|
| DB 01 |
B36 |
Y |
P |
|
|
| DB 01 |
R37 |
Y |
P |
|
|
| DB 01 |
W37 |
Y |
P |
|
|
| DB 01 |
B37 |
Y |
P |
|
|
| DB 01 |
R45 |
Y |
P |
|
|
| DB 01 |
W45 |
Y |
P |
|
|
| DB 01 |
B45 |
Y |
P |
|
|
| DB 01 |
R46 |
Y |
P |
|
|
| DB 01 |
W46 |
Y |
P |
|
|
| DB 01 |
B46 |
Y |
P |
|
|
| DB 01 |
R47 |
Y |
P |
|
|
| DB 01 |
W47 |
Y |
P |
|
|
| DB 01 |
B47 |
Y |
P |
|
|
| DB 01 |
R48 |
Y |
P |
|
|
| DB 01 |
W48 |
Y |
P |
|
|
| DB 01 |
B48 |
Y |
P |
|
|
| DB 01 |
R49 |
Y |
P |
|
|
| DB 01 |
W49 |
Y |
P |
|
|
| DB 01 |
B49 |
Y |
P |
|
|
| DB 01 |
R50 |
Y |
P |
|
|
| DB 01 |
W50 |
Y |
P |
|
|
| DB 01 |
B50 |
Y |
P |
|
|
| DB 01 |
R56 |
Y |
P |
|
|
| DB 01 |
W56 |
Y |
P |
|
|
| DB 01 |
B56 |
Y |
P |
|
|
| DB 01 |
R58 |
Y |
P |
|
|
| DB 01 |
W58 |
Y |
P |
|
|
| DB 01 |
B58 |
Y |
P |
|
|
| DB 02 |
1 |
Y |
P |
|
|
| DB 02 |
2 |
Y |
P |
|
|
| DB 02 |
3 |
Y |
P |
|
|
| DB 02 |
4 |
Y |
P |
|
|
| DB 02 |
5 |
Y |
P |
|
|
| DB 02 |
6 |
Y |
P |
|
|
| DB 02 |
8 |
Y |
P |
|
|
| DB 02 |
9 |
Y |
P |
|
|
| DB 02 |
10 |
Y |
P |
|
|
| DB 02 |
11 |
Y |
P |
|
|
| DB 02 |
12 |
Y |
P |
|
|
| DB 02 |
13 |
Y |
P |
|
|
| DB 02 |
14 |
Y |
P |
|
|
| DB 02 |
15 |
Y |
P |
|
|
| DB 02 |
16 |
Y |
P |
|
|
| DB 02 |
17 |
Y |
P |
|
|
| DB 02 |
18 |
Y |
P |
|
|
| DB 02 |
19 |
Y |
P |
|
|
| DB 02 |
20 |
Y |
P |
|
|
| DB 02 |
21 |
Y |
P |
|
|
| DB 02 |
23 |
Y |
P |
|
|
| DB 02 |
25 |
Y |
P |
|
|
| DB 02 |
26 |
Y |
P |
|
|
| DB 02 |
27 |
Y |
P |
|
|
| DB 02 |
28 |
Y |
P |
|
|
| DB 02 |
29 |
Y |
P |
|
|
| DB 02 |
30 |
Y |
P |
|
|
| DB 02 |
31 |
Y |
P |
|
|
| DB 02 |
33 |
Y |
P |
|
|
| DB 02 |
35 |
Y |
P |
|
|
|
|---|
| THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
|---|
| SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| HTML Block |
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| db 01 |
2 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
4 |
S |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
6 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
7 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
9 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
10 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
13 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
14 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
16 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
17 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
18 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
19 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
20 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
21 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
22 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
23 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
24 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
26 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
27 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
28 |
s |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
31 |
r |
N |
N |
N |
F |
Failed 90 Min Test |
Y |
N |
| db 01 |
33 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
35 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
36 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
37 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
38 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
39 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
40 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
41 |
r |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
42 |
r |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| HTML Block |
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| db 01 |
1 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
3 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
5 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
8 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
11 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
12 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
15 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
25 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
29 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
30 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
32 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
34 |
Y |
Y |
Y |
P |
|
|
|
| db 01 |
43 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| HTML Block |
|
|---|
| General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
|---|
| HTML Block |
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
|---|
| Lighting Report | | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
| 400w hibay |
Y |
| 400w low bay |
Y |
| 400w low bay defused |
Y |
| 12 volt holgen down lights |
Y |
| led down lights sal |
Y |
| 1 by 36w defused battens |
Y |
| 1 by 30w defused battens |
Y |
| jumbo exit |
Y |
| 2 by par 38 spot |
Y |
| 1 by 30w defused emergency batten dual opperation |
Y |
| oaster light |
Y |
| led oaster light |
Y |
| 150w round mh shop light |
Y |
| exits |
Y |
| 2 by 36w defused emergency batten |
Y |
| spit fire emergency |
Y |
| 40w batten |
Y |
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| 400W HIGHBAY |
BoH AISLE |
2 |
NOT OPERATIONAL |
N |
TBA |
TBA |
ADDED TO FORTNIGHTLY REPAIRS REPORT |
| 400W HIGHBAY |
ABOVE MASSAGE/SOUNDBARS |
1 |
NOT OPERATIONAL |
N |
TBA |
TBA |
ADDED TO FORTNIGHTLY REPAIRS REPORT |
| 400W HIGHBAY |
ABOVE FLOOR CARE |
2 |
NOT OPERATIONAKL |
N |
TBA |
TBA |
ADDED TO FORTNIGHTLY REPAIRS REPORT |
| 400W HIGHBAY |
ABOVE LAPTOPS |
1 |
NOT OPERATIONAL |
N |
TBA |
TBA |
ADDED TO FORTNIGHTLY REPAIRS REPORT |
| 400 W HIGHBAY |
ABOVE OVENS/COOKTOPS |
2 |
NOT OPERATIONAL |
N |
TBA |
TBA |
ADDED TO FORTNIGHTLY REPAIRS REPORT |
| RECESSED EM LIGHT |
31 |
1 |
FAIL EM TEST |
Y |
N |
N |
REPLACED |
|
|---|
| Site Status Selector | Store now fully compliant |
|---|